UPS2000-G- (6 kVA-20 kVA)
User Manual
Issue 18 (2021-07-16)
Table 4-28 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/
UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item
Description
Equalized
Determine whether to enable
charging
equalized charging. The
parameter is configurable in
any mode.
Time
Set the time interval for
interval
equalized charging. The
parameter is configurable in
any mode.
Voltage
Set the battery equalized
voltage. The parameter is
configurable in any mode.
Max.
Set the maximum equalized
current
current. The parameter is
configurable in any mode.
Max. time Set the maximum equalized
charge time. The parameter
is configurable in any mode.
Float Charge screen
Figure 4-39 Float Charge screen
Table 4-29 Float Charge screen
Item
Description
Voltage
Set the battery float voltage. The
parameter is configurable in any
mode.
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Default
Value Range
Value
Enabled
Disabled,
Enabled
60 days
30–180 days
2.35 V/cell
2.33–2.40 V/cell
2.0 A
Standard model:
1.0–2.0 A
Long backup
time model:
1.0–4.0 A
960 min
600–999 min
Defa
Value Range
ult
Valu
e
2.25
2.25–2.30 V/cell
V/cell
74