Huawei UPS2000-G-6KRTS User Manual page 179

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G- (6 kVA-20 kVA)
User Manual
Alarm
Alarm
ID-
Name
Cause
ID
0136-01
Faulty
tempera
ture
and
humidit
y
module
0158-01
On
bypass
Issue 18 (2021-07-16)
Alarm
Alarm
Severit
Clearan
y
ce
Mode
Minor
Minor
Automa
tic
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
If the bypass is abnormal,
the UPS may power off.
D Alarm Handling
Handling Suggestion
Possible causes: The
temperature and
humidity module is
faulty.
Measures:
● Check parameter
settings of the
temperature and
humidity transducer.
● Replace the
temperature and
humidity transducer.
Possible causes:
● The inverter is not
started.
● The load exceeds the
rated inverter
loading capacity.
● The inverter is faulty.
Measures:
● Check whether other
alarms are
generated. If yes, see
the other handling
methods.
● If no, start the UPS
manually.
171