Huawei UPS2000-G-6KRTS User Manual page 142

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G- (6 kVA-20 kVA)
User Manual
Mai
Second-
n
Level
Men
Menu
u
System
Paramete
rs
Issue 18 (2021-07-16)
Third-Level
Fourth-Level
Menu
Menu
Faulty UPS
-
(Dry
contact)
Parallel
Single/
(configurabl
Parallel
e after the
Redundant
inverter
UPSs
shuts down)
Output
Output mode
(configurabl
(configurable
e after the
only on the
inverter
UPS2000-
shuts down)
G-15 kVA/20
kVA)
Voltage level
Frequency
level
Converter
mode
Output
Volt. adj. coef. ±5%, ±4%, ±3%, ±2%,
(configurabl
e in any
mode)
Bypass
Max. voltage
(configurabl
e after the
Min. voltage
inverter
shuts down)
Copyright © Huawei Technologies Co., Ltd.
Value Range
Dry contacts 1–6
Single and Parallel
0–3
Single-phase/Three-
phase
● 208 V, 220 V, 230 V,
and 240 V (on the
UPS2000-G-6
kVA/10 kVA)
● 208 V, 220 V, 230 V,
and 240 V, single-
phase (on the
UPS2000-G-15
kVA/20 kVA)
● 380 V, 400 V, and
415 V, three-phase
(on the UPS2000-
G-15 kVA/20 kVA)
50 Hz, 60 Hz, and
Automatic
Enabled and Disabled
±1%,0%
10%, 15%, 20%, 25%,
and 30%
10%, 20%, 30%, 40%,
50%, and 60%
C LCD Menus and Parameters
Preset Value
Dry contact 6
Single
0
Three-phase (on the
UPS2000-G-15 kVA/20
kVA)
● 220 V (on the
UPS2000-G-6
kVA/10 kVA)
● 220 V, single-phase
(on the UPS2000-
G-15 kVA/20 kVA)
● 380 V, three-phase
(on the UPS2000-
G-15 kVA/20 kVA)
50 Hz
Disabled
0%
15%
20%
134