Huawei UPS2000-G-6KRTS User Manual page 80

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G- (6 kVA-20 kVA)
User Manual
Issue 18 (2021-07-16)
Table 4-26 Basic screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-
G-15KRTL/UPS2000-G-20KRTL)
Item
Description
Number
Set the number of batteries.
of
When the number of
batteries/
batteries N is less than 20,
Positive
the system output power is
batteries
derated to N/20 in battery
and
mode. The parameter is
Negative
configurable in non-battery
batteries
mode or non-battery ECO
mode. You need to set
Number of batteries on the
UPS2000-G-6 kVA/10 kVA,
and set two battery strings
(positive and negative) on
the UPS2000-G-15 kVA/20
kVA.
Battery
Set the battery string
capacity
capacity. (Battery capacity is
the sum of each battery
string. Set the battery
capacity based on the
actual value.) The
parameter is configurable in
non-battery mode or non-
battery ECO mode.
Intelli.
When it is set to enabled,
Hibernati
the intelligent battery
on
hibernation function is
enabled. The parameter is
configurable in any mode.
Overtemp
Set an alarm threshold for
. thres.
high battery temperatures.
The parameter is
configurable in any mode.
Undertem
Set an alarm threshold for
p. thres.
low battery temperatures.
The parameter is
configurable in any mode.
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Default Value
Value Range
0
16–20
6 kVA standard
7–1000 Ah
model: 7 Ah
6 kVA long
backup time
model: 40 Ah
10 kVA
standard
model: 9 Ah
10 kVA long
backup time
model: 65 Ah
15 kVA/20 kVA
long backup
time model: 65
Ah
Disabled
Disabled,
Enabled
50°C
45–55°C
–5°C
–30°C to +5°C
72