ABB ACS880-107LC Hardware Manual page 77

Inverter units
Hide thumbs Also See for ACS880-107LC:

Advertisement

Notes:
1)
See section
The XD2D connector (page
2)
See chapter
The Safe torque off function (page
3)
0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use. 1 =
Acceleration/deceleration ramps defined by parameters 23.14/23.15 in use.
4)
Constant speed 1 is defined by parameter 22.26.
5)
See section
DIIL input (page
6)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by
DIO1 and DIO2.
7)
Determines whether DICOM is separated from DIOGND (ie. common reference for digital
inputs floats; in practice, selects whether the digital inputs are used in current sinking or
sourcing mode). See also
DICOM=DIOGND ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND separate.
8)
Current [0(4)...20 mA, R
selected by switch AI1. Change of setting requires reboot of control unit.
9)
Current [0(4)...20 mA, R
selected by switch AI2. Change of setting requires reboot of control unit.
Additional information on the connections
External power supply for the control unit (XPOW)
The control unit is powered from a 24 V DC, 2 A supply through terminal block XPOW. With
a type BCU control unit, a second supply can be connected to the same terminal block for
redundancy.
Using an external supply is recommended if
• the control unit needs to be kept operational during input power breaks, for example,
because of continuous fieldbus communication
• immediate restart is needed after a power break (that is, no control unit power-up delay
is allowed).
DI6 as a PTC sensor input
PTC sensors can be connected to this input for motor temperature measurement as follows.
The sensor can alternatively be connected to FEN-xx encoder interface module or FPTC-xx
thermistor protection module (option +L536) or PTC relay (option +L505). At the sensor end
of the cable, leave the shields unconnected or ground them indirectly via a high-frequency
capacitor with a few nanofarads, for example 3.3 nF / 630 V. The shield can also be grounded
directly at both ends if they are in the same ground line with no significant voltage drop
between the end points. See the firmware manual of the inverter unit for parameter settings.
+t°
+t°
1
One to six PTC thermistors connected in series
78).
BCU-x2 ground isolation diagram (page
= 100 ohm] or voltage [0(2)...10 V, R
in
= 100 ohm] or voltage [0(2)...10 V, R
in
+t°
+t°
79).
83).
1
+t°
+t°
Control units of the drive 77
82).
> 200 kohm] input
in
> 200 kohm] input
in
+24V
...
DI6