118 Technical data
Terminal and cable entry data for power cables
The locations and sizes of the cable entries and input power connections are shown by the
dimension drawings delivered with the drive.
Drawings of output connections are shown in chapter
Terminal data for the inverter control unit
See chapter
Control units of the drive (page
Input power (DC) connection
Voltage (U
)
1
Drive AC supply network type
Motor (AC) connection
Motor types
Voltage (U
)
2
Frequency (f
)
2
Current
Switching frequency
Maximum motor cable length
Output terminals
Efficiency
98.5 ... 98.7% at nominal power level depending on drive type.
The efficiency is not calculated according to IEC 61800-9-2.
Dimensions (page
73).
ACS880-107LC-xxxxx-7: 709...976 V DC. This is indicated in the
type designation label as typical input voltage levels (742/849/976
V DC).
TN (grounded) and IT (ungrounded) systems, corner-grounded
systems up to 600 V AC
Asynchronous AC induction motors, permanent magnet synchron-
ous motors and AC induction servomotors, ABB synchronous re-
luctance (SynRM) motors
0 to AC supply voltage of drive, 3-phase symmetrical, U
weakening point
0...500 Hz
•For higher operational output frequencies, please contact your
local ABB representative.
•Operation outside the range of 12...150 Hz requires derating.
See section
Derating (page
See section Ratings.
3 kHz (typical).
The switching frequency can vary per frame and voltage. For exact
values, contact your local ABB representative.
500 m (1640 ft)
Note: Longer cables cause a motor voltage decrease which limits
the available motor power. The decrease depends on the motor
cable length and characteristics. Contact ABB for more information.
See chapter Dimensions.
125).
max
111).
at field