The alarm pressure switch functions to energize the alarm if coolant pressure is denied
the process.
G.
Level Switch
1.
Most models include a level switch that monitors the
tank fluid level and provides a warning when the tank
level is low and needs to be refilled.
2.
The chiller will start up the pump when a low level
condition exists. If the low level condition continues
after about one minute a low level fault is displayed the
instrument.
3.
The alarm may be silenced by pressing the
green button.
4.
The fault will continue to be shown on the
instrument display. The usual home screen
will not be visible.
5.
The setpoint can be checked and changed
through the menu system and the "To Process Temp" is available in the sensor
section.
6.
The compressor will activate and provide cooling if needed after its 3 minute
delay, but the fault screen will still be on the home screen until the water level
satisfies the level switch.