Chilled Water Piping Installation - Advantage Engineering Titan Instruction Manual

Table of Contents

Advertisement

Titan Central Chillers
2.1
GENERAL
A.
Chillers are shipped skid mounted and wrapped in plastic prior to shipment. Check the
overall condition of the equipment prior to accepting delivery. Check for visible damage
and document any evident damage on the delivery receipt. Shipping damage is the
responsibility of the carrier.
B.
All process piping materials (such as hose, rigid piping, valves or filters) used in process
water piping circuitry must be rated for 100°F minimum temperature and 100 PSI
minimum pressure.
C.
All such materials must have the equivalent or larger diameter of the particular process
connection that length of process water piping is connected to.
2.2
UNIT LOCATION
A.
Foundation. The chiller must be installed on a rigid and level mounting surface with
adequate strength to support the operating weight of the chiller including the weight of
water and attached piping.
B.
Air-cooled units include an indoor portion (chiller) and remote outdoor condenser. The
indoor unit contains the refrigeration circuits, pumping station and microprocessor control
and is located inside the facility. The remote air-cooled condenser is located outside the
facility.
C.
Water-cooled units include the refrigeration circuits, pumping station, microprocessor
control and water-cooled condenser on a single skid.
D.
For most efficient operation, locate the water-cooled unit and the air-cooled chiller in a
level, clean, dry and well ventilated environment. Please note the air-cooled condenser
(air-cooled models only) is located outside of the facility.
2.3

CHILLED WATER PIPING INSTALLATION

A.
There are two piping connections on the unit. One is labeled TO PROCESS, and the
other is labeled FROM PROCESS. Refer to typical drawings for recommended piping
practices or optional plant layout drawing if supplied.
Typical reservoir lid and
From Process opening.
525 East Stop 18 Road Greenwood, Indiana 46142
Email: service@AdvantageEngineering.com
Typical To Process Port.
ADVANTAGE ENGINEERING, INC.
317-887-0729
Fax: 317-881-1277
Service Department Fax: 317-885-8683
Page: 14