Titan Central Chillers
2.5

AIR-COOLED CONDENSER (TI-A MODELS)

A.
Air-cooled units have an indoor portion that contains the chiller's compressor, evaporator,
control system and pumping station and a remote outdoor condenser that discharges the
process heat outdoors.
1.
The indoor portion of the system containing the compressor, evaporator, control
system and pumping stations should be installed in a clean, dry and well
ventilated environment.
2.
The remote air-cooled condenser is designed for outdoor installation normally
selected for ambient air temperatures from -20°F minimum to 95°F maximum.
Ambient conditions outside of the rated temperatures may require an alternate
selections for proper operations.
B.
Refrigerant piping for remote outdoor condenser models:
1.
Only refrigerant grade copper and solder shall be used.
2.
The refrigerant line sizes shall be based on equivalent line lengths and
acceptable refrigerant pressure drops.
3.
A certified refrigerant technician shall evacuate and charge the refrigerant system
under loaded conditions.
Typical Water-Cooled Condenser Connections
TI-60W shown with optional standby pump
and manifold.
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
Condenser Water Out
Fax: 317-881-1277
Condenser
From Process
To Process
Water In
This label marks the
Condenser Water In
connection
Condenser
Condenser
From Process
To Process
Water Out
Water In
This label marks the
connection
Page: 16

Advertisement

Table of Contents
loading

Table of Contents