Titan Central Chillers
To Process
50°F
S e t p o i n t : 50°F
Circulating
2.
Once acknowledged, the unit will control to the new setpoint temperature. Press
the Back button repeatedly to return to the Setpoints screen or press the home
button to return to the Home screen.
To Process
Setpoints
50°F
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
S e t p o i n t : 50°F
Circulating
Back
Pick
Go
C.
Hi Deviation. The High Deviation value programs the controller to sound the alarm if the
process temperature exceeds the set difference from setpoint. For example, Hi Deviation
= 10°F, Setpoint = 50°F. Hi deviation alarm will sound if the temperature reaches 60°F.
Setpoints
To Process
50°F
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
S e t p o i n t : 50°F
Circulating
Back
Pick
Go
1.
The factory default is 10°. The range for the Hi Deviation is from 0°F - 50°F.
2.
Once acknowledged, press the Back button repeatedly to return to the Setpoints
screen or press the home button to return to the Home screen.
D.
Lo Deviation. The Lo Deviation value programs the controller to sound the alarm if the
process temperature exceeds the set difference from setpoint. For example, Lo Deviation
= 10°F, Setpoint = 50°F. Lo deviation alarm will sound if the temperature cools to 40°F.
Setpoints
To Process
50°F
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
S e t p o i n t : 50°F
Circulating
Back
Pick
Go
1.
The factory default is 10°. The range for the Lo Deviation is from 0°F - 50°F.
2.
Once acknowledged, press the Back button repeatedly to return to the Setpoints
screen or press the home button to return to the Home screen.
D.
Low Flow (optional feature not included on all units). The Low Flow value programs
the controller to sound an alarm if the process flow goes below the low flow set value.
Main Menu
To Process
50°F
Setpoints
Utilities
Network
Flow
Options
S e t p o i n t : 50°F
Machine
Circulating
Back
Pick
Go
To Process
Process Setpoint
50°F
50°F
S e t p o i n t : 50°F
Circulating
Cancel
Adjust
OK
Hi Deviation
To Process
50°F
10°F
S e t p o i n t : 50°F
Circulating
Cancel
Adjust
OK
Lo Deviation
To Process
50°F
10°F
S e t p o i n t : 50°F
Circulating
Cancel
Adjust
OK
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729
Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
Setpoints
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
Back
Pick
Go
To Process
Change Setting
50°F
Process Setpoint
Success
S e t p o i n t : 50°F
Circulating
Acknowledge
To Process
Change Setting
50°F
Hi Deviation
Success
S e t p o i n t : 50°F
Circulating
Acknowledge
To Process
Change Setting
50°F
Lo Deviation
Success
S e t p o i n t : 50°F
Circulating
Acknowledge
Page: 37