Titan Central Chillers
WARNING: Do not connect the unit to a voltage supply not equal to the unit's voltage
requirements as specified on the unit's data plate. Use of incorrect voltage will void the unit's
warranty and cause a significant hazard that may result in serious personal injury and unit
damage.
WARNING: Electric Shock Hazard. High Voltage is present in the electrical cabinet. Disconnect
power before servicing. Follow all facility lock-out tag-out procedures.
6.
Voltage supplies must be within +/- 10% of the name
plate voltage and must be within 2% from leg to leg.
Extreme voltage imbalance or using the wrong voltage
can damage your chiller and cause premature unit
failure as well as a safety risk.
7.
A proper ground is required for the unit.
B.
CONTROL CIRCUIT WIRING
1.
The unit's supplied control circuit is 110 volt, 1 phase,
60 cycle.
2.
The control circuit is supplied by the factory installed
transformer. A control circuit fuse is provided.
C.
GENERAL
1.
Make certain all ground connections to the unit are properly affixed.
2.
Make certain power conductor, disconnecting means, and fusing are properly
sized according to the unit's power supply requirements.
3.
Follow all local and national codes.
4.
Make certain that all owner and factory wire connections are tight before applying
power to the unit.