Advantage Engineering Titan Instruction Manual page 29

Table of Contents

Advertisement

Titan Central Chillers
f.
2.
If the unit is phased incorrectly, the operator must:
a.
b.
C.
PROCESS FLOW ADJUSTMENTS
1.
The operator must determine and set proper water flow rate for the most efficient
and trouble free operation.
a.
b.
2.
Excessive flow will cause the motor to operate at high amperage and
eventually open the thermal overload safety shutting off the motor. To
correct this problem, a throttling valve must be installed in the from process line.
With the throttling valve fully closed, slowly open the valve until the correct motor
amperage is achieved. Motor amperage rating may be acquired on the motor
nameplate.
3.
Low flow may result in poor temperature control and high temperature
rises. To correct this problem, a bypass system must be installed between the to
and from process lines. With the bypass valve fully closed, slowly open the valve
until the correct motor amperage is achieved. Motor amperage rating may be
acquired on the motor nameplate.
D.
ADJUSTMENT OF CENTRIFUGAL PUMP. When starting a piece of equipment with a
centrifugal pump, it is important to properly set the flow rate to prevent overloading of the
Incorrect rotation is "counter-clockwise" (incorrect phase) when viewed
from the rear of the motor. If the shaft does not rotate when the ON/OFF
SWITCH is on, the operator must identify the cause as outlined in the
troubleshooting and repair section of this manual.
If the motor shaft is phased correctly (shaft turns in a clockwise
direction), continue with step C. If the motor shaft is NOT phased
correctly (shaft turns in a counter-clockwise direction), correct as outlined
in step 2.
Disengage the electrical power supply to the unit at the unit's disconnect
switch. Follow all facility proper lock-out tag-out procedures before
proceeding.
Once the electrical power supply is disengaged the operator can change
rotation by switching any two power conductors at the terminal block or
customer supplied main power disconnect.
Water flow rate through the process is determined by the pressure losses
in the process loop. Generally, higher flow rates result in turbulent flow
achieving maximum temperature control and lower maintenance. Since
the evaporator in most liquid chillers is flow sensitive, the efficiency of
operation is directly related to the flow of liquid.
Maximum chiller efficiency is obtained at approximately 2.4 gpm per
ton of rated capacity. Low liquid flow can reduce efficiency and in some
cases allow ice to develop in the evaporator which can damage the
evaporator. Excessive liquid flow will trip the motor overload protection
circuit.
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
Fax: 317-881-1277
Page: 29

Advertisement

Table of Contents
loading

Table of Contents