Instrument : Flow Menu (Option) - Advantage Engineering Titan Instruction Manual

Table of Contents

Advertisement

Titan Central Chillers
3.9

INSTRUMENT : FLOW MENU (Option)

A.
The Flow Menu is only functional when the optional flow meter is installed. Items in the
Flow Menu are Enable, Offset and Calibration.
Main Menu
To Process
To Process
50°F
50°F
Setpoints
Utilities
Network
Flow
Options
S e t p o i n t : 50°F
S e t p o i n t : 50°F
Machine
Circulating
Circulating
Back
Pick
Go
B.
Advance to the Flow Enable / Disable screen. Select Enabled to enable the flow option.
To Process
To Process
Flow
50°F
50°F
Enable
Offset
Calibration
S e t p o i n t : 50°F
S e t p o i n t : 50°F
Circulating
Circulating
Back
Pick
Go
C.
Offset. This allows the user to select the flow offset according to the pump horsepower.
To Process
To Process
Flow
50°F
50°F
Enable
Offset
Calibration
S e t p o i n t : 50°F
S e t p o i n t : 50°F
Circulating
Circulating
Back
Pick
Go
1.
These values should be factory set and should not be changed. Adjust only if
they are set to values other than the factory default.
D.
Calibration. This allows the user to calibrate the unit's flow meter.
To Process
To Process
Flow
50°F
50°F
Enable
Offset
Calibration
S e t p o i n t : 50°F
S e t p o i n t : 50°F
Circulating
Circulating
Back
Pick
Go
1.
Using a reliable and accurate external flow meter the user can input a calibration
constant value in the screen so that the unit flow display matches the external
flow meter.
2.
Use the Up or Down arrow keys to input the value and then press the Select
button to save and confirm success.
Main Menu
To Process
50°F
Setpoints
Utilities
Network
Flow
Options
S e t p o i n t : 50°F
Machine
Circulating
Back
Pick
Go
To Process
Flow
50°F
Enable
Disable
S e t p o i n t : 50°F
Circulating
Back
Pick
Go
To Process
Offset
50°F
-3 GPM
S e t p o i n t : 50°F
Circulating
Back
Pick
Go
Calibration
To Process
50°F
770
S e t p o i n t : 50°F
Circulating
Back
Pick
Go
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729
Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
FLow
Enable
Offset
Calibration
Back
Pick
Go
To Process
FLow
Change Setting
50°F
Enable
Flow Enable
Offset
Success
Calibration
S e t p o i n t : 50°F
Circulating
Back
Acknowledge
Pick
Go
To Process
FLow
Change Setting
50°F
Enable
Offset
Offset
Success
Calibration
S e t p o i n t : 50°F
Circulating
Back
Acknowledge
Pick
Go
To Process
FLow
Change Setting
50°F
Enable
Calibration
Offset
Success
Calibration
S e t p o i n t : 50°F
Circulating
Back
Acknowledge
Pick
Go
Page: 41