Air-Cooled Piping Installation (Typical) - Advantage Engineering Titan Instruction Manual

Table of Contents

Advertisement

Titan Central Chillers
2.8

Air-Cooled piping installation (typical)

1.
Chiller (air-condensed, 2 pump system with standby pump)
2.
Water make-up connection (chiller reservoir)
3.
From city water supply (reservoir make up)
4.
Overflow connection (chiller reservoir)
5.
Pump discharge connection (supply to process)
6.
Condenser (Zone #1, remote outdoor unit, mounted at ground level on concrete pad or on roof)
7.
Condenser (Zone #2, remote outdoor unit, mounted at ground level on concrete pad or on roof)
8.
Condenser refrigeration piping (sized by refrigeration contractor based on specific installation)
9.
Reservoir Drain Connection
10. Filter (MLS Series In-Line full flow design - see piping options)
11. Water inlet connection (filter)
12. Water outlet connection (filter)
13. Bypass pipe with valves (redirection of process water flow during filter service)
14. Drain-back dam (keeps header pipes full during shut-down periods)
15. Main header valves (closed for header service or during use of alternate source of cooling water)
16. Alternate source of cooling water on/off valve (for system emergency back up)
17. Alternate water supply source (for system emergency back up)
8
26
1
3
2
5
6
14
25
15
14
15
4
12
9
10
11
13
525 East Stop 18 Road Greenwood, Indiana 46142
Email: service@AdvantageEngineering.com
18. System multi-use open drain (reservoir overflow,
reservoir drain, system emergency back up)
19. Process water drops from header to use point
(valved for service shutoff)
20. Pressure gauge and thermometer (for system
performance monitoring and evaluation)
21. Header ends valved and capped (for future expan-
7
sion)
22. Header by-pass valve (adjustable and pressure
activated to maintain flow in header during low
process demand)
23. Branch header valves (for branch header service
isolation)
24. Branch header
25. Valve to open drain (for system emergency back-
up)
26. From process return pipe
This drawing is supplied to demonstrate a possible piping
configuration for the equipment and is general in nature
showing pipe sizes and basic routing. It is not intended to
be inclusive of every detail required for specific location
and installation. Consult with a professional engineer to
determine specific needs before installation.
23
16
19
19
18
17
ADVANTAGE ENGINEERING, INC.
317-887-0729
Fax: 317-881-1277
Service Department Fax: 317-885-8683
24
24
23
22
20
21
21
Page: 22