Titan Central Chillers
Titan Central Chillers
3.4

MG INSTRUMENT OPERATION

MG Series Control. This control instrument is used on units with fixed displacement
compressors.
A.
INSTRUMENT START-UP
1.
When the correct electrical power and adequate water supply pressure are
supplied to the unit, it is possible to start the unit.
2.
Upon powered up, the instrument displays the Standby Screen.
a.
b.
Status : Ready indicates the unit is ready to start and there are no faults
preventing operation.
To Process
50°F
Standby
Status : Ready
S e t p o i n t : 50°F
Status
Circulating
Ready
Status : Not Ready.
After applying power a screen that reads "Not Ready" typically
indicates the presence of a sensor probe fault, pressure switch
fault or motor overload fault. See the troubleshooting and
maintenance portions of the manual for additional Information.
The fault must be corrected in order to continue operation of the
unit.
To Process
50°F
Status : Not Ready
Standby
S e t p o i n t : 50°F
Status
Circulating
Not Ready