Titan Central Chillers
WARNING: Check local codes to determine proper use of back flow prevention device in water
make-up supply line.
2.7

ELECTRICAL CONNECTION

A.
STANDARD MODELS
1.
All electrical wiring must comply with local codes and the National Electric Code.
2.
Electrical power supply requirements for standard units are identified on the
equipment data tag. Determine that the plant's voltage supply is the same as the
unit's voltage requirements, taking into account the SSCR Rating.
3.
A customer supplied, four conductor cable is required for connection to a
customer supplied fused disconnecting means. The fused disconnecting means
shall be sized and installed according to the unit's power supply requirements
and local electrical codes. (Some custom units may include a fused or non-fused
disconnect switch.)
4.
Connect the four conductor power cable to the power entry terminal block on
the unit's electrical panel. Then connect the power cable to the fused disconnect
switch. There is no power entry hole into the electrical cabinet. This allows the
matching of the entry hole size and location to the customer supplied fittings.
5.
A unit specific electrical drawing is shipped with the unit.
Typical location of Water Supply connection.
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
Fax: 317-881-1277
Page: 19