4. SETUP AND PROCEDURES PRIOR TO OPERATION

4.6 Wiring the Data Link Cable

4.6.1 Wiring the CC-Link dedicated cable

M
aster module
(Blue)
(White)
Terminating
(Yellow)
*1
resistor
(110Ω, 1/2W)
4 - 11
The following describes how to wire the CC-Link dedicated cable when connecting the
RFID interface module to a CC-Link system.
The following shows an example of connecting the CC-Link dedicated cable to the
RFID interface module.
RFID interface module
CC-link dedicated cable
*1. When using a Ver. 1.10 compatible CC-Link dedicated cable or CC-Link dedicated
cable (Ver. 1.00 compatible), connect the 110Ω 1/2W (brown, brown, brown)
terminating resistors. When using a CC-Link dedicated high performance cable (Ver.
1.00 compatible), connect the 130Ω 1/2W (brown, orange, brown) terminating resistors.
Point
Always connect the "terminating resistors" that come with the master module to the
modules on both ends of the data link. (Connect across DA-DB.)
(Blue)
(Blue)
(White)
(White)
(Yellow)
(Yellow)
CC-link dedicated cable
I/O module, etc.
(Blue)
(White)
Terminating
(Yellow)
*1
resistor
(110Ω, 1/2W)
4 - 11