3. SPECIFICATIONS
*1
Setting Value
0000
Continually executes the ID command until there is a response from an ID tag.
Stops the ID command due to a tag not present error when an ID tag is not detected within the set value
0001 to 9999
[BCD] x 0.1 seconds, causing error detection to turn ON.
3 - 17
(4) Auto system command wait time setting area (RWwm+3H)
The auto system command wait time setting area sets the time that an auto
system command (auto, repeat auto, FIFO repeat) is to wait for an ID tag
response after the ID command execution request (RYn4) is turned ON.
Operation is performed based on the settings at the time that the initial data setting
request flag (RY(n+k)9) turns on.
Table 3.15 Auto System Command Wait Time Setting Area
*1. If a value other than BCD is set, error detection (RXn5) turns ON. The set contents are not updated.
*2. The default setting is 0000H (the ID command is continually executed until there is a
response from an ID tag).
(5) Module status storage area (RWrm+0H)
Refer to Section 3.6.2 (5) "Module status storage area (RWrm+0H)".
(6) Error details storage area (RWrm+1H)
Bit 0 (ID command error) of the error details storage area turns ON when the initial
data setting request flag (RY(n+k)9) is turned ON and an out-of-range value is
specified in the communication specification area (RWwm+0H) or the processing
specification area (RWwm+2H).
When the initial data setting request flag (RY(n+k)9) is turned OFF, the bit of the
error details storage area (RWrm+1H) is cleared.
*2
Description
3 - 17