YASKAWA V1000 Installation Manual page 40

Hide thumbs Also See for V1000:
Table of Contents

Advertisement

8 Output Assemblies (Drive Consumes)
u
Extended Speed Control Output - 21 (0x15)
Output
Word
Instance
0
21
1
Name
Run Fwd
Run Rev
Fault Reset
NetCtrl
NetRef
Speed Reference
40
Byte
Bit 7
Bit 6
0
NetRef
1
2
3
Forward Run Command
0: Stop
1: Forward Run
Reverse Run Command
0: Stop
1: Reverse Run
Fault Reset
(0 to 1 transition: Fault Reset)
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference/2
SS
Setting range: 0 to 0xFFFF
For example, when setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/2
Unit depends on o1-03.
YASKAWA ELECTRIC TOBP C730600 60C V1000 Option SI-EN3/V Installation Manual
Bit 5
Bit 4
NetCtrl
Speed Reference (Low Byte)
Speed Reference (High Byte)
Description
(SS: Speed scale)
2
= 1024 = 0x0400
Bit 3
Bit 2
Fault
Reset
Bit 1
Bit 0
Run
Run
Rev
Fwd

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Si-en3/v

Table of Contents