Configuration 6 / 9 - LG MultiSITE MS8250 User Manual

Vav room controller
Hide thumbs Also See for MultiSITE MS8250:
Table of Contents

Advertisement

CONFIGURATION SCREENS

Configuration 6 / 9

Configuration 6 / 9
Figure 27: Configuration 6 / 9 Display.
6/9 Configuration
Standby mode
Standby diff.
Standby time
Unocc. time
Temp. occ. time
Table 20: Configuration 6 / 9 Parameter Details.
Configuration Parameters Default Value
Standby Mode (Standby Mode
Configuration)
Default Value: Absolute
Standby diff. (Standby Temperature
Differential)
Default Value: 4.0°F (2.0°C)
Standby Time
Default: 0.5 hours
Unocc. Time (Unoccupied Time)
Default: 0.0 hours
Temp. Ccc. Time (Temporary Occupancy
Time)
Default Value: 2 hours
38
Absolute
4.0 °F
0.5 hrs
0.0 hrs
2.0 hrs
Standby setpoints used for control.
Absolute: Standby entered values are used for standby mode.
Offset: Occupied setpoints +/- Standby diff. used for standby mode.
Refer to "Setpoints Screens" on page 49 to define Standby cool and Standby heat values.
Choices: Absolute or Offset.
When Standby mode is set to "offset", standby setpoints are calculated as follows:
Standby cool: Cool setpoint + Standby diff.
Standby heat: Heat setpoint - Standby diff.
Refer to "Setpoints Screens" on page 49 to define Standby cool and Standby heat values.
Range: 1.0°F (0.5°C) to 5.0°F (2.5°C), using 1.0°F (0.5°C) increments.
Time between the moment where the motion sensor detects last movement in the area, and
the time which the Room Controller stand-by setpoints become active.
This parameter is not active when the "Door" function is used (wired or wireless).
Range: 0.5 to 24.0 hours, using 0.5 hour increments.
Time between the moment where the Room Controller toggles to stand-by mode, and the
time which the Room Controller unoccupied mode and setpoints become active.
Default value of 0.0 hours disables the unoccupied timer. This prevents the Controller from being
able to switch from stand-by mode to unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours (0.5 hour increments).
The time the Room Controller stays in override mode before reverting back to unoccupied
mode. When the Room Controller is in unoccupied mode, pressing the on-screen Over-
ride icon or closing the contact on UI17, configured as "Remote Override", sets the Room
Controller to Override mode for defined time period, and uses the Occupied Cooling and
Heating setpoints.
Range: 0.0 to 24.0 hours
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Significance and Adjustments

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multisite vucqms8250

Table of Contents