Pressure Independent, continued.
Figure 32: Balancing PI 1 / 2 Display.
1 /2 Ba lanc ing
A i r f l ow level
0 C FM
0 CF M
A ir fl o w set po int
Mi n . flow
3 4 0 CF M
Ma x. co ol flow
3 4 0 CF M
Ma x. he at flow
3 4 0 CF M
R ehe at flow
3 4 0 CF M
Table 25: Pressure Independent Balancing Options Screen 1 of 2.
Configuration Parameter
Airflow Level
Read Only
Airflow Setpoint
Read Only
Min. Flow (Minimum Airflow)
Default value: 340 CFM (160 l/s)
Max. Cool Flow (Maximum Cooling
Airflow)
Default Value: 340 CFM (160 l/s)
Max. Heat Flow (Maximum Heating
Airflow)
Default Value: 340 CFM (160 l/s)
Reheat Flow (Maximum Reheat
Airflow)
Default Value: 340 CFM (160 l/s)
BACnet
AV110 (R)
AI350 (R)
AV250 (R/W)
AV252 (R/W)
AV251 (R/W)
AV253 (R/W)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
BALANCING
Pressure Independent
Function Description
Measured (calibrated) airflow.
Range: 0 to 20000 CFM (0 to 9440 l/s).
Current active airflow setpoint.
Airflow Setpoint is not displayed when Damper Over-
ride is Open or Closed.
Range: 0 to 10000 CFM (0 to 4720 l/s).
Minimum airflow supplied to the zone.
Range: 40 to 800 CFM (19 to 377 l/s).
Maximum airflow supplied to the zone when cooling.
Range: 40 to 800 CFM (19 to 377 l/s).
Maximum airflow supplied to the zone when heating.
Range: 40 to 800 CFM (19 to 377 l/s).
Maximum airflow supplied to the zone with duct
reheat.
Range: 40 to 800 CFM (19 to 377 l/s).
45