TEST OUTPUTS SCREENS
Test Outputs Screens, continued.
These parameters can also be changed via BACnet; the changed parameter background will turn red to indicate the parameter's value had
been overridden. The overridden value remains even if the user exits the main screen.
Test Outputs values are LIVE. Any output gets displayed immediately for any value change according to the following:
1. If any BACnet priority array (1 - 16) includes a value, the displayed state background shows in red.
2. When toggling a value on the screen, the output directly energizes according to the selected value.
3. After any output state gets modified, all overrides get cancelled after one (1) minute of button inactivity, or if scrolling from one (1) screen
to another screen.
Test Outputs UO9 to UO12 are dependent on control type configuration. Analog or Binary options may be shown depending on the configura-
tion of Actuator type, Fan type, Reheat config and Duct heater outputs.