The thermocouple-input module has the PLC CPU and the buffer memories for data communications.

6.1 Buffer Memory Configuration

The followings describe buffer memory configuration.

6.1.1 G3F-TC4A Buffer Memory

0
Channel enable/disable Specification
1
Specifying the type of thermocouple for channel 0
2
Specifying the type of thermocouple for channel 1
3
Specifying the type of thermocouple for channel 2
4
Specifying the type of thermocouple for channel 3
5
Specifying the type of thermocouple for channel 4
6
Specifying the type of thermocouple for channel 5
7
Specifying the type of thermocouple for channel 6
8
Specifying the type of thermocouple for channel 7
9
Specifying the type of thermocouple for channel 8
10
Specifying the type of thermocouple for channel 9
11
Specifying the type of thermocouple for channel 10
12
Specifying the type of thermocouple for channel 11
13
Specifying the type of thermocouple for channel 12
14
Specifying the type of thermocouple for channel 13
15
Specifying the type of thermocouple for channel 14
16
Specifying the type of thermocouple for channel 15
17
Temperature conversion value of the channel 0
18
Digital conversion value of the channel 0
19
Error code of the channel 0
20
Temperature conversion value of the channel 1
21
Digital conversion value of the channel 1
22
Error code of the channel 1
23
Temperature conversion value of the channel 2
24
Digital conversion value of the channel 2
25
Error code of the channel 2
26
Temperature conversion value of the channel 3
27
Digital conversion value of the channel 3
28
Error code of the channel 3
29
Temperature conversion value of the channel 4
30
Digital conversion value of the channel 4
31
Error code of the channel 4
Function
6 - 1
Description
Bit On(1): Enable, Bit Off(0) : Disable
0
K
-200.0 to 1200.0°C
1
J
-200.0 to 800.0°C
2
E
-150.0 to 600.0°C
3
T
-200.0 to 400.0°C
4
B
400.0 to 1800.0°C
0.0 to 1750.0 °C
5
R
6
S
0.0 to 1750.0°C
If a value outside the defined range is set,
the bit of address 67 that corresponds to
the channel turns on and the thermocouple
type will be set to type K.
• Temperature conversion value
: 10 times of a real temperature is displayed.
• Digital conversion value
If a temperature conversion value is converted
into a value within 0 to 16000, that value is a
digital conversion value.
It can be used as a process value of the PID
control module.
Expression
Digital conversion value = (16000/
measuring temperature range) ×
(temperature conversion value –
minimum measuring temperature)
• Error code
16 : Disconnection detection error
17 : Upper or lower overflow
18 : Reference junction compensation device
error
Disable R/W
Type K R/W
Read
Only

Hide quick links: