LG MultiSITE MS8250 User Manual page 46

Vav room controller
Hide thumbs Also See for MultiSITE MS8250:
Table of Contents

Advertisement

BALANCING
Pressure Independent
Pressure Independent, continued.
Figure 33: Balancing PI 2 / 2 Display.
2 /2 Ba lanc ing
A i r f l ow level
0 C FM
A ir fl o w set po int
0 CF M
D am p . overrid e
Min im um
B al ometer
0 CF M
Mi n f l ow of f set
0 CF M
M ax f lo w of f set
0 CF M
Table 26: Pressure Independent Balancing Options Screen 2 of 2.
Configuration Parameter
Airflow Level
Read Only
Airflow Setpoint
Read Only
Damp. Override (Damper Override))
Default Value: None
Balometer (Measured Airflow From
Balometer)
Default Value: 0 CFM (0 l/s)
Minflow Offset (Minimum Airflow
Calibration Offset)
Default Value: 0 CFM (0 l/s)
Max Flow Offset (Maximum Airflow
Calibration Offset)
Default Value: 0 CFM (0 l/s)
46
BACnet
Measured (calibrated) airflow:
AV110 (R)
Range: 0 to 20000 CFM (0 to 9440 l/s).
Current active airflow setpoint.
AI350 (R)
Airflow Setpoint is not displayed when Damper Override is Open or Closed.
Range: 0 to 10000 CFM (0 to 4720 l/s).
Force damper to selected position during balancing.
0 - None: No damper override. Damper under normal control.
1 - Minimum: Force damper to maintain minimum airflow setpoint.
2 - Max. cool: Force damper to maintain maximum cooling airflow setpoint.
MV172 (R/W)
3 - Close: Force damper closed.
4 - Reheat: Force damper to maintain maximum reheat airflow setpoint.
5 - Open: Force damper fully open.
Choices: None, Minimum, Max. cool, Close, Reheat and Open.
Measured value will be used to update calibration Offset and ensure mea-
sured Airflow level matches Balometer reading.
N/A
Balometer is displayed when Damper Override is Minimum or Max. cool.
Range: 0 to 20000 CFM (0 to 9440 l/s)
Calibration offset applied to Airflow Level at Minimum flow.
AV258
Min flow offset is displayed when Damper Override is Minimum.
Range: -5000 to 5000 CFM (0 to 30932 l/s).
Calibration offset applied to Airflow Level at Maximum flow.
AV259
Max flow offset is displayed when Damper Override is Max. cool.
Range: -5000 to 5000 CFM (0 to 30932 l/s).