PRESSURE CONTROL VALVE
DISPLAY NAVIGATION
Info Menu
(LCD & LCD Setup)
Once the PCV has 24VAC power applied to it and the LCD Setup Tool is plugged into the Service Port, the thermostat screen will
go through the initial start-up screen. The display should indicate that this is a Pressure Controller, and not something different.
To view basic information on the PCV controller, press the 'Menu' button
button.
APPLICATION
PRESSURE CTRL
VENT PRESSURE
0.150 IN H20
SUPPLYAIRTEMP
85.0F
DAMPER POSITION
50%
AIRHANDLER IS
ACTIVE
MAC ADDRESS 1
DEVICE INSTANCE 101
PRESS MENU
TO EXIT
Air terminal, pressure controller, dual duct or fan powered terminal unit
Current pressure reading
If supply air temperature probe is not present, LCD will display no probe.
If supply air temperature probe is present, LCD will display temperature.
This indicates the current position of the damper as percent (%)
Range is 0-100% (100% = full open or maximum air)
When pressure is sensed, this status is active.
When no pressure is sensed, status is inactive.
Shows the BACnet MAC address – range is 1-99
If no BACnet module attached, LCD will display MAC address None
Displays controller's BACnet Device Instance (if BACnet module is attached)
Device Instance can range from 0-4, 194, 303
NOTE:
Service menu will automatically time out after 20 seconds
once and scroll through with the 'Down' arrow
priceindustries.com | PRESSURE CONTROL VALVE - Manual