PRESSURE CONTROL VALVE
DISPLAY NAVIGATION

Discharge Air Temperature Menu

NOTE:
Thermostat must remain connected in this application
(Application Specific Options)
Scroll through menu with Up and Down keys. Press 'Enter/Menu' button to apply your changes. *---Saving---* will display as your
changes are applied.
DISCHARGETEMP
(when Analog DAT Control enabled)
DAT HEAT/COOL: When discharge air is 2° below room temp, it is considered cooling;
when discharge air is 2° above room temp, it is considered heating.
DAT CTRL MODE
This mode is recommended because PCV (with DAT enabled) will monitor and use the
DAT HEAT/COOL
discharge air to control the analog outputs to help satisfy room load.
DAT HEAT ONLY, DAT COOL ONLY: Heat Only, Cool only always assumes cold or hot.
These modes are not recommended.
DISCHARGE AIR TEMP.
Current temperature of the probe mounted to water pipe
NO PROBE
DAT COOL SETPOINT
Cooling setpoint
55.0°F
DAT HEAT SETPOINT
Heating setpoinit
90.0°F
DAT WHILE PI IS IN
The temperature that will be maintained when the system is satisfied
DEADBAND 0.0°F
DAT UNOCC SET
DAT Unoccupied Setpoint.
DISABLED
Default: Disabled
DAT SERVICE TIME
DAT will calculate and move the valve every 60 seconds (default)
60 SEC
DAT STEP DIVISION
Distance a single step travels (leave at default 3)
3
DAT STEP MAXIMUM
Maximum change a call for heating or cooling can make during a step
10%
DAT DIFFERENTIAL
The range that the controller is satisfied and will not make adjustments
2.0°F
PRESS MENU
TO EDIT
priceindustries.com | PRESSURE CONTROL VALVE - Manual
11