PRESSURE CONTROL VALVE
DISPLAY NAVIGATION
Stat Setup Menu
(Stat Options)
Scroll through menu with Up and Down keys. Press 'Enter/Menu' button to apply your changes. *---Saving---* will display as your
changes are applied.
STAT SETUP
(Motion Sensor STAT only)
Off - motion sensor disabled - default for regular LCD stat
MOTION ENABLE OFF
On - motion sensor enabled (only enabled if you have a motion stat)
Only visible with motion stat
(Motion Sensor STAT only)
Sets the sensitivity of the motion sensor
MOTION SENSITIVITY
1 - least sensitive
5
9 - most sensitive
5 - default
Only visible when motion is enabled
PCV will go into unoccupied after no motion is detected and this timer expires
HVAC TIMEOUT
240 MINUTES
Default: 240 minutes
(Use room light output to select lighting signal)
LIGHTS TIMEOUT
PCV will turn off lighting output after no motion is detected and this timer expires
60 MINUTES
Default: 60 minutes
Always on (default)
LCD BACKLIGHT
Always off
ALWAYS ON
Button push - lights up on button press
BACK LIGHT COLOR
Change the back light color
AQUA
On (default) - stat will beep when a user tries to exceed a limit
SOUND OPTIONS
ON
Off
CONTROLLER NAME
Set a custom name for stat
PRESS MENU
TO EXIT
priceindustries.com | PRESSURE CONTROL VALVE - Manual
15