Hardware Specifications - Price PCV Series Manual

Pressure control valve
Table of Contents

Advertisement

PRESSURE CONTROL VALVE
MAINTENANCE

Hardware Specifications

Power Requirements
Ambient Ratings
Outputs
Inputs
Communication ports
Size
Weight
24VAC, 47-63 Hz 6VA (not including output loading) NEC Class II
32º to 131º F (0º to 55º C) 10 to 90% RH (non-condensing)
24VAC Binary Output. Max 0.5Amps each, MAX 1.85A total Switched HOT or Switched COMMON
Fan
Stages of heat or heat open/close (x3)
Cooling
Damper CW
Damper CCW
Analog 0-10VDC (x4). Max: 10mA each
Fan (ECM)
Heat
Cool
Aux
Thermistor Sensor (10k Type J thermistor)
Analog 0-10V inputs (x2). 20k ohm input impedance
Thermostat Inputs
Room Setpoint Dial
Temperature Sensor (10K Type J Thermistor)
Accuracy of +/- 0.5°F from 55°F to 85°F (+/ 0.25°C from 13°C to 25°C)
Pressure Transducer (Kavlico Differential transducer)
0-2"
Pressure Range:
BACnet MS/TP Connection (optional)
Communication speeds: 9,600, 19,200, 38,400, 76,800 (default)
Maximum recommended devices per MS/TP segment: 30 devices
For local setup using Price USB LINKER service tool
11" x 5.75" x 2.75"
1.8lb. (816g)
priceindustries.com | PRESSURE CONTROL VALVE - Manual