PRESSURE CONTROL VALVE
DISPLAY NAVIGATION

Setpoint Menu

NOTE:
Does not apply to pressure controller applications
(Setpoint Limits and Temperature Units)
Scroll through menu with Up and Down keys. Press 'Enter/Menu' button to apply your changes. *---Saving---* will display as your
changes are applied.
SETPOINT
10
PRESSURE CONTROL VALVE - Manual | priceindustries.com
SET LOW LIMIT
This is the lowest setpoint allowed
65.0F
Range: 10.0°F - 100.0°F, Default: 65.0°F
SET HIGH LIMIT
This is the highest setpoint allowed
80.0F
Range: 10.0°F - 100.0°F, Default: 80.0°F
TEMPERATURE UNITS
Fahrenheit or Celsius
FAHRENHEIT
Default: °F
NIGHT HEAT SET
PIC will maintain this heating setpoint when unoccupied
62.0F
Range: 10.0°F - 100.0°F, Default: 62.0°F
NIGHT COOL SET
PIC will maintain this cooling setpoint when unoccupied
83.0F
Range: 10.0°F - 100.0°F, Default: 83.0°F
Default: 2°F, 1°C
PROPORTIONAL BAND
2.0F
Proportional Band is the raneg of control or the throttling range of the device
1°F, 0.5°C
DAY DIFFERENTIAL
1.0F
Day Differential is the deadband on either side of the setpoint
PRESS MENU
TO EXIT