PRESSURE CONTROL VALVE
DISPLAY NAVIGATION
P/C Setup
(Pressure Controller Setup)
Scroll through menu with Up and Down keys. Press 'Enter/Menu' button to apply your changes. *---Saving---* will display as your
changes are applied.
P/C SETUP
16
PRESSURE CONTROL VALVE - Manual | priceindustries.com
VENT PRESSURE
0.150 IN H20
PRESSURE SETPOINT
0.150 IN H2O
CONTROL TYPE BYPASS
DEADBAND
0.030 IN H2O
DPR RUNTIME
95 SEC
MAX STEP
5%
AF FAIL NSB
ENABLED
UNOCC DPR POS
50%
PRESS MENU
TO EXIT
Current pressure reading
Pressure setting can be adjusted to maintain a constant duct static pressure (default: 0.150
in H2O)
Bypass: (Default) Throttles the bypass valve to maintain constant pressure set point
Downstream: Constant pressure downstream - throttles the inline valve to maintain constant
downstream pressure setpoint
Deadband on either side of the pressure setpoint (default: 0.030 in H2O)
Damper runtime in seconds (default: 95 sec, recommended not to change)
Maximum amount that output will be changed per step
Range: 1 - 50% (default: 5%)
Airflow Fail NSB (Night Setback) Enabled: PCV controller will go into unoccupied mode when
no pressure is measured
If unoccupied signal is enabled, PCV damper will go into position (default: 50%)