PRESSURE CONTROL VALVE
BACNET NETWORKING
BACnet Service Menu Continued
Each controller's MAC address, Device Instance, and Baud rate are set in the BACnet sub-menu of the service menu accessed
through an LCD thermostat or LCD setup tool. For information on how to select a MAC address and Device Instance for any
controller on a network, see the following pages.
To set the controller's BACnet settings, enter the Service Menu and adjust settings as follows:
When the screen displays a flashing value, that value is ready to be changed and can be adjusted by pressing the arrow
NOTE:
keys. Pressing Menu will save the value.
BAUD RATE
76800
Once all settings are made, scroll down to press Menu to exit. The controller will then re-start, this is because all BACnet info is
only read once at startup. If you had left the MAC set in hardware, and adjusted the DIP switch settings to set the MAC address,
you would have to manually restart the controller by cycling 24 VAC power for the new MAC address to take effect (setting through
software makes the restart happen automatically however).
22
PRESSURE CONTROL VALVE - Manual | priceindustries.com
THEN
OR
The baud rate is the speed that the MS/TP network runs at.
EVERY device on the network must run at the same speed.
Price controllers are defaulted to a baud rate of 73800, but can
be changed to 38400, 19200, or 9600. For a network segment
with all Price controllers (including Price PRTU systems), it's
recommended that the baud rate be left at 76800.
*Choose lower baud rates only when integrating with devices
by other manufacturers whose maximum speed is lower than
76800 (eg. 38400).