PRESSURE CONTROL VALVE
DISPLAY NAVIGATION
Output Menu – Heat
(Setup of Heat Outputs)
Scroll through menu with Up and Down keys. Press 'Enter/Menu' button to apply your changes. *---Saving---* will display as your
changes are applied.
OUTPUT
OUTPUT FAN
OUTPUT HEAT
ANALOG DAT CONTROL
PRESS MENU
TO EXIT
REHEAT TYPE
BINARY
DRIVE TIME
95 SECONDS
HEAT STAGE 1
1%
HEAT STAGE 2
50%
HEAT STAGE 3
100%
AF INTERLOCK
DISABLED
REHEAT FAIL SAFE
DISABLED
ANALOG HEAT MIN
0.0 VDC
ANALOG HEAT MAX
10.0 VDC
ANALOG HEAT IDLE
0.0 VDC
PRESS MENU
TO EXIT
Enable or disable Discharge Air Temperature control
Reheat Type: Binary, Hot Water, Binary/PWM, Hot Water/PWM
Binary uses Stage 1, 2, 3 - Default
Hot water uses Stage 1 & 2 for Open/Close
Binary/PWM and Hot Water/PWM - Stage 3 is PWM
Hot water runtime in seconds
Not shown if binary heat is used
Heat Stage 1 Trip Point: Stage 1 engages at 1% heating
Not shown if hot water heat is used
Heat Stage 2 Trip Point: Stage 2 engages at 50% heating
Not shown if hot water heat is used
Heat Stage 3 Trip Point: Stage 3 engages at 100% heating
Disabled: (Default) The controller will enable the heat as normal
Enabled: The heating outputs will not energize until at least 87.5%
Disabled – Outputs send 24VAC on call for heat
Enabled – Outputs send 24VAC when no call for heat (fail open valve in cold climates)
Outputs this voltage on heat analog pin when there is a minimum call for heating
Outputs this voltage on heat analog pin when there is a maximum call for heating
Outputs this voltage on heat analog pin when there is no call for heating