PRESSURE CONTROL VALVE
DISPLAY NAVIGATION

BACnet Menu

(BACnet Addressing Setup)
Scroll through menu with Up and Down keys. Press 'Enter/Menu' button to apply your changes. *---Saving---* will display as your
changes are applied.
BACNET
14
PRESSURE CONTROL VALVE - Manual | priceindustries.com
Hardware - uses DIP switch on BACnet module for MAC Address - Default (not
recommended)
MAC SET IN:
Software - uses STAT to set MAC Address - this overrides the hardware DIP switches
HARDWARE
NOTE:
Example: MAC Address = 1, Device Instance = 100 - total address for this PIC would be
101
MAC ADDRESS
Display current MAC Address
HARDWARE: 1
NOTE:
This is the software BACnet address & must be unique on your building site
Range: 1 - 4, 194, 303
NOTE:
to apply the address changes.
DEVICE INSTANCE
Addresses are only read on startupt, so after any changes you must reset the controller
either via STAT (which is automatic) or cycle 24VAC power
NOTE:
improperly set DIP switches from popping up all over a network, which would be extremely
difficult to troubleshoot
This sets the BACnet MS/TP baud rate
9600 baud - slowest
BAUD RATE 76800
19200 baud
38400 baud
76800 baud (Default baud rate for Price products) - fastest
PRESS MENU
TO EXIT
the MAC Address (range 1-99) is added to the Device Instance
MAC Address only read on startup - see Device Instance below
After changing the Device Instance the STAT will send a Reset command to the PIC
Addresses are only read on startup to prevent a controller with faulty/damaged/