Balancing Instructions - Price PCV Series Manual

Pressure control valve
Table of Contents

Advertisement

PRESSURE CONTROL VALVE
DISPLAY NAVIGATION
Support: Having difficulty installing or configuring this product? Price is here to help.
Controls Application Support: 204.654.5613 | controls@priceindustries.com | priceindustries.com/resources/type/literature

Balancing Instructions

For more advanced setup details, please see 'Display Navigation' section.
THEN
5 SECONDS
SERVICE MENU:
APPLICATION
SERVICE MENU:
BALANCING
DPR. OVERRIDE:
DISABLED
DPR OVERRIDE:
GOTO FULL OPN
POS.
TARGET
50%
100%
6
PRESSURE CONTROL VALVE - Manual | priceindustries.com
THEN
THEN
THEN
Hold down the Menu button on the LCD Thermostat for
5 seconds until prompted for a passcode; use
to enter the passcode; DOWN, UP, UP, DOWN.
The screen will now display "Service Menu: Application."
Scroll down to the Balancing sub-menu.
Press the Menu button to enter this menu.
Screen will now show "Damper Override Disabled." Press
Menu, and now "Disabled" will be flashing; this means you can
now scroll UP or DOWN with the arrow keys to select a target
to send the damper to.
For most applications, you will want to select "Go To Full
Open," and once selected, the thermostat will read the damper
position and target position as the damper drives open.
and