Setting The Device Instance - Price PCV Series Manual

Pressure control valve
Table of Contents

Advertisement

PRESSURE CONTROL VALVE
BACNET NETWORKING
Setting the Device Instance (Coupled MAC and DI)
Device Instance:
A Device Instance number identifies a device within an entire building, therefore giving it a unique number or Address,
much like a telephone ext. number. A building can have one telephone number, but all the extensions have a unique
number to identify them. A Device Instance number would work the same way and must be unique throughout the building.
The Device Instance number is user set through the LCD Thermostat or the LCD-SETUP tool.
Below is a table defining how a Device Instance number is obtained.
NOTE:
Each device on a network segment must be set to run at the same speed or baud rate.
Description
MAC Address
Tier1 (x100)
Tier2 (x10,000)
Tier3 (x1,000,000)
Example Device Instance setup with Default settings:
• MAC Address = 6 (6 x 1 = 6) – Set through software
+
TIER 1 = 58 (58 x 100 = 5800) – Set through software
+
TIER 2 = 1 (1 x 10,000 = 10,000) – Set through software
+
TIER 3 = 0 (0 x 1,000,000 = 1,000,000) – Set through software
=
Final Device Instance = 0,015,806
LCD-SETUP
Default Value (Factory)
6
58
1
0
0
01
58
Tier3
Tier2
Tier1
Multiplier
Multiplier
Multiplier
06
MAC
Address
TECH TIP
When using a PCV controller and no LCD
thermostats are on site, you must purchase
a setup tool in AIO known as a LCD-SETUP
and use this to configure the PCV controller.
Remember all settings are stored in the PCV
Controller and not the thermostat.
priceindustries.com | PRESSURE CONTROL VALVE - Manual
Notes
Value: limited to 1-99
Value: limited to 0-99
Value: limited to 0-99
Value: limited to 0-4