Burkert 3360 Quick Start Manual
Burkert 3360 Quick Start Manual

Burkert 3360 Quick Start Manual

Electromotive control valve
Hide thumbs Also See for 3360:
Table of Contents

Advertisement

Quick Links

Type 3360, 3361
Electromotive control valve
Elektromotorisches Regelventil
Vanne de régulation électromotorisée
Quickstart
English
Deutsch
Français

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3360 and is the answer not in the manual?

Questions and answers

Summary of Contents for Burkert 3360

  • Page 1 Type 3360, 3361 Electromotive control valve Elektromotorisches Regelventil Vanne de régulation électromotorisée Quickstart English Deutsch Français...
  • Page 2 We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous réserve de modifications techniques. © Bürkert Werke GmbH, 2016 Operating Instructions 1606/04_EU-ML_00810487 / Original DE...
  • Page 3: Table Of Contents

    Type 3360 and 3361 Contents  1 THE QUICKSTART ..................4 8 ELECTRICAL INSTALLATION ............... 20 Definition of the term "device" ..........4 Electrical installation with circular plug-in connector ..20 Symbols ..................5 Electrical installation with cable gland ........23 2 INTENDED USE .....................5 9 START-UP ....................
  • Page 4: The Quickstart

    A detailed description can be found 13.3 Access to the büS Service interface ........48 in the operating instructions for Type 3360 and 3361. Keep the quickstart in a location which is easily accessible to every 14 MAINTENANCE, TROUBLESHOOTING .........
  • Page 5: Symbols

    Type 3360 and 3361 Intendeduse Symbols INTENDED USE The following symbols are used in these instructions. Non-authorized use of the electromotive control valve Type 3360 and 3361 may be a hazard to people, nearby DANGER! equipment and the environment. Warns of an immediate danger. The electromotive control valve Type 3360 and 3361 is ▶ Failure to observe the warning will result in fatal or serious injuries. designed to control the flow of liquid and gaseous media. ▶ Standard devices must not be used in the potentially explosive area.
  • Page 6: Basic Safety Instructions

    Type 3360 and 3361 Basicsafetyinstructions BASIC SAFETY INSTRUCTIONS Danger due to an uncontrolled process in the event of These safety instructions do not consider any contingencies or incidents a power failure. which occur during installation, operation and maintenance. If devices do not have the optional SAFEPOS energy-pack, the valve The operator is responsible for observing the location-specific safety remains in an undefined position in the event of a power failure.
  • Page 7: General Information

    The warranty is only valid if the device is used as intended in accordance with the specified application conditions. Information on the Internet Operating instructions and data sheets for Types 3360 and 3361 can be found on the Internet at: www.burkert.com...
  • Page 8: Structure And Function

    Direction of flow direction of flow direction of flow Angle seat control valve Globe control valve Type 3360 Type 3361 Fig. 1: Incoming flow under the seat, direction of flow Fig. 2: Structure, electromotive control valve Type 3360 and 3361 english...
  • Page 9: Display Of The Device State

    Conformity closed green* The electromotive control valves Type 3360 and 3361 are compliant * F actory setting; colors can be changed (see software description with with EC directives as stated in the EC Declaration of Conformity. reference to Type 3360-3361 at www.burkert.com).
  • Page 10: Rating Plate

    Type 3360 and 3361 Technicaldata Rating plate Operating conditions For operation of the device observe the product-specific Direction of flow, actuator size (nominal force) information on the rating plate. Material valve body, line connection Da (ø outer) Di (ø inner), WARNING! flow capacity Malfunction if the temperature exceeds or drops below the Maximum permitted medium pressure, seal material, permitted temperature range.
  • Page 11 Type 3360 and 3361 Technicaldata Direction of flow: is specified on the rating plate by an arrow and the numbers 1 and 2. The 1 and the 2 stand for identification also on the valve body. The incoming flow is under the seat.
  • Page 12: General Technical Data

    Type 3360 and 3361 Technicaldata General technical data 6.5.1 Electrical data Protection class: 3 in accordance with DIN EN 61140 Materials Actuator: PPS and aluminum (VDE 0140) powder-coated Valve body: 316L Electrical connections Body connection: 316L / 1.4401 Devices with Spindle: 1.4401 / 1.4404...
  • Page 13 The determined service life of 2.5 years was determined under the fol- lowing conditions: Ambient temperature 40 °C Medium pressure in [bar] Medium temperature 180 °C Duty cycle 100% Fig. 5: Energy consumption actuator Type 3360 Medium pressure 5 bar Orifice DN32 english...
  • Page 14 Type 3360 and 3361 Technicaldata Analog output NOTE! (optional) Consider voltage drop in supply line. Max. current: 10 mA (for voltage output 0...5/10 V) For example, a cable cross-section of 0.34 mm must not exceed 0...800 Ω (for current output 0/4...20 mA) Burden (load): a line length of 8 meters for a copper cable.
  • Page 15: Installation Of The Valve

    Type 3360 and 3361 Installationofthevalve INSTALLATION OF THE VALVE Filter: Required for devices with approval in accordance with EN 161. In accordance with DIN EN 161 "Automatic Shut-off Valves for Gas WARNING! Burners and Gas Appliances", a strainer must be installed upstream of the valve in the pipeline to prevent a 1 mm test pin from penetrating.
  • Page 16: Installation Of Devices With Welded Connection

    Type 3360 and 3361 Installationofthevalve Installation of devices with welded 7.2.2 Removing the actuator → connection Clamp the valve body into a holding fixture. → The electromotive control valves must not be welded with mounted Place a suitable open-end wrench on the body connection.
  • Page 17 Type 3360 and 3361 Installationofthevalve 7.2.3 Installation requirements 7.2.5 Mounting actuator on the valve body Installation position: any position → Before mounting the actuator, check whether the graphite Direction of flow: is specified on the rating plate by an arrow and the seal of the valve body is available and undamaged.
  • Page 18 Type 3360 and 3361 Installationofthevalve WARNING! Holding device To protect the valve actuator from damage due to forces Risk of injury due to non-observance of the tightening torque. and vibrations, a holding device is recommended. This is Non-observance of the tightening torque is hazardous as the available as an accessory. See operating instructions on the device may be damaged.
  • Page 19: Rotating The Actuator

    Type 3360 and 3361 Installationofthevalve Rotating the actuator The position of the connections can be aligned by rotating the actuator through 360°. NOTE! Damage to the valve seat seal and valve seat contour when valve is closed. Rotate clockwise If the valve is closed when the actuator is rotated, the valve seat seal and the valve seat contour may be damaged.
  • Page 20: Electrical Installation

    The electromotive control valve is available with one of 2 different Using the set-point value input 4...20 mA connections: If several devices of Type 3360 or 3361 are connected in series and the power supply to a device in this series con- • With circular plug-in connector (multipole version) nection fails, the input of the failed device becomes highly •...
  • Page 21 Type 3360 and 3361 Installationofthevalve 8.1.3 X3 – M12 circular plug, 4-pole or 5-pole, Selection of the connection line: operating voltage When selecting the length and cross-section of the indi- vidual wires, consider the voltage drop with reference to the Wire color Assignment maximum supply current.
  • Page 22 Type 3360 and 3361 Installationofthevalve 8.1.4 X1 – M12 circular plug, 8-pole 8.1.5 X2 – M12 socket, 5-pole, input signals process actual value (for process Pin Wire (From point of view of the device) Assignment controller function only) color* On the...
  • Page 23: Electrical Installation With Cable Gland

    Using the set-point value input 4...20 mA Inputs / Outputs → PV → ANALOG.type If several devices of Type 3360 or 3361 are connected in (signal source: PV.source → Analog). series and the power supply to a device in this series con- Tab.
  • Page 24 Type 3360 and 3361 Installationofthevalve 8.2.2 Access to the connection terminals 2. Removing LED and storage module: → Remove the 2 fastening screws (hexagon head key, width across To access the terminals, open the device as described below. flats 3 mm). 1. Remove display module or dummy cover: → Take hold of the LED and storage module on both sides of the NOTE! metal housing and lift out.
  • Page 25 Type 3360 and 3361 Installationofthevalve NOTE! Connection terminals Damage or malfunction due to ingress of dirt and moisture. To comply with the degree of protection IP65: ▶ Close all unused cable glands with dummy plugs. ▶ Tighten the union nuts on the cable glands. Tightening torque depends on cable size or dummy plug approx. 1.5 Nm (1.1 lbf ft).
  • Page 26 Type 3360 and 3361 Installationofthevalve 8.2.4 Terminal assignment – input signal from * E lectrical installation of büS network: the control center (e.g. PLC) Terminals 1, 2 and 3 (CAN interface) are for the connection of the büS network. Terminal Assignment (From point of view of the device)
  • Page 27 Type 3360 and 3361 Installationofthevalve 8.2.7 Terminal assignment – process actual On the Signal value input (for process controller Terminal Assignment device External circuit type* side function only) Frequency not used On the Signal - externally PV1: clock input + Clock+ Terminal Assignment...
  • Page 28 Type 3360 and 3361 Installationofthevalve 8.2.8 Closing the device Dummy cover NOTE! or display module Damage or malfunction due to ingress of dirt and moisture. Before closing the device, comply with the degree of protection IP65 by ensuring: LED and storage module ▶ that the seal is inserted in the actuator housing/actuator cover and is not damaged.
  • Page 29: Start-Up

    Type 3360 and 3361 Start-up → START-UP To release, rotate the dummy cover counter-clockwise by 90° and remove from the actuator housing. → WARNING! Push DIP switch 4 downwards. The device is in the AUTOMATIC operating state. Risk of injury from improper operation. Improper operation may result in injuries as well as damage to the DIP switches device and the environment.
  • Page 30: Setting Options For Start-Up

    Type 3360 and 3361 Start-up Setting options for start-up Basic settings • Setting with the PC software Bürkert-Communicator on the 9.3.1 Basic settings position control PC or tablet The position control is delivered with the basic settings made This type of setting is possible for all device types and device at the factory.
  • Page 31: Setting Safety Position

    2) The P.TUNE function supports the setting up of the process control by automatic optimization of the process parameters. The fine adjustment of the process parameters is described in the Type of basic setting Factory presetting software description with reference to Type 3360, 3361. (Observe sequence) 1. Setting safety position Close Setting safety position 2.
  • Page 32: Adjust The Position Control - Running X.tune

    Type 3360 and 3361 Start-up → Select FUNCTION. Adjust the position control – running X.TUNE The following safety positions can be selected: When the X.TUNE function is running, the position control is adjusted Close Valve tightly closed. to the physical stroke of the actuating element used.
  • Page 33 Type 3360 and 3361 Start-up 9.5.1 Adjustment using the buttons in the 9.5.2 Adjustment via PC or display on the device device The 2 buttons for running the X.TUNE are located under the dummy The setting is made on the PC via the büS Service interface cover.
  • Page 34: Set Standard Signal For Set-Point Position

    Type 3360 and 3361 Start-up → Set standard signal for set-point Select seal material. position The following question appears: “Do you really want to start the X.TUNE? Setting option: Do not start the X.TUNE unless it is absolutely essential to Using the PC software Bürkert-Communicator or on the run the X.TUNE.
  • Page 35: Select Physical Unit For Process Control

    Type 3360 and 3361 Start-up Select physical unit for process Parameterize process values control Setting option: Using the PC software Bürkert-Communicator or on the Setting option: display of the device (option) Using the PC software Bürkert-Communicator or on the display of the device (option)
  • Page 36: Scaling Process Control

    Type 3360 and 3361 Start-up Scaling the process set-point value: Scaling process control → Select SP .scale. The scaling of the process control affects the following functions: → • Dead band of the process control Input minimum and maximum. • Sealing function (CUTOFF), if the process control (P.CO) has You have parameterized the process set-point value.
  • Page 37: Setting Dead Band Of The Process Control

    Type 3360 and 3361 Start-up 9.10 Setting dead band of the process 9.11 Set up process control – run P.LIN, control P.TUNE Setting option: Setting option: Using the PC software Bürkert-Communicator or on the Using the PC software Bürkert-Communicator or on the...
  • Page 38: Operation

    Type 3360 and 3361 Operation → OPERATION Start P.LIN. The P.LIN function is running. WARNING! 9.11.2 Adjustment to process control (P.TUNE) Danger due to improper operation. Improper operation may result in injuries as well as damage to the Running the P.TUNE function: device and the area around it.
  • Page 39: Control Elements

    Type 3360 and 3361 Operation 10.1.1 LED illuminated ring 10.2 Control elements The transparent LED illuminated ring, which transmits the light of the LEDs outwards, is attached to the dummy cover or display module. SIM card The device status is indicated by a lit, flashing or rapidly flashing LED illuminated ring in one color or in alternating colors.
  • Page 40: Display Operation (Option)

    Type 3360 and 3361 Displayoperation(option) 10.2.2 OPEN button and CLOSE button DISPLAY OPERATION (OPTION) The device is operated and set via a display with a touch-screen. Electrical manual Open valve: Press OPEN button control: Close valve: Press CLOSE button 11.1 User interface Running X.TUNE...
  • Page 41: Description Of The Keys

    Type 3360 and 3361 Displayoperation(option) 11.2 Description of the keys 11.3 Display views You go from the start screen to the following views: Functions • Configuration view, using the left navigation key Press briefly: Back • View 2...4 created by the user, using the right navigation...
  • Page 42: Description Of The Symbols

    Type 3360 and 3361 Displayoperation(option) 11.4 Description of the symbols Symbols for indicating the device status according to NAMUR NE 107 Symbols for user rights If several device statuses exist simultaneously, the device status with Symbol Description the highest priority is displayed. Priority Symbol Description The setting is write-protected and can be changed Failure, error or fault! with the appropriate user right/user code only.
  • Page 43: Manual Actuation Of The Valve

    Type 3360 and 3361 Manualactuationofthevalve Symbols for indicating the operating states MANUAL ACTUATION OF THE VALVE Priority Symbol Description The control valve can be manually actuated in 2 ways: electrically or mechanically. Device has stopped control mode due to a serious error. The valve remains in its Electrical manual control is usually used to open and close the valve position.
  • Page 44 Type 3360 and 3361 Manualactuationofthevalve Switch to MANUAL operating state: 12.1.2 Devices without display module The 2 buttons for opening and closing the valve are located under the → To switch to MANUAL operating state, briefly press the dummy cover. Menu key. The HAND symbol can be seen on the information bar.
  • Page 45: Actuating Valve Mechanically

    Type 3360 and 3361 Manualactuationofthevalve Switch to MANUAL operating state: 12.2 Actuating valve mechanically → Set DIP switch 4 to ON. The device is now in MANUAL operating When the supply voltage is not applied, e.g. during installation or in state (see “Fig. 25”).
  • Page 46 Type 3360 and 3361 Manualactuationofthevalve → To adjust the valve, use an Allen key with 4 mm width across flats. Open Mechanical Manual NOTE! valve Control Maximum tightening torque 2 Nm (1.5 lbf ft). If the tightening torque is exceeded on reaching the valve end position, the mechanical manual control will be damaged.
  • Page 47: Fieldbus Gateway Ethernet/Ip

    Type 3360 and 3361 Manualactuationofthevalve FIELDBUS GATEWAY ETHERNET/IP 13.2 Electrical connection The EtherNet/IP is connected with a circular plug-in connector M12, 4-pole. Display Pin 1 Transmit + module Pin 2 Receive + Pin 3 Transmit – Fieldbus Pin 4 Receive –...
  • Page 48: Access To The Büs Service Interface

    Type 3360 and 3361 Maintenance,Troubleshooting 13.3 Access to the büS Service interface MAINTENANCE, TROUBLESHOOTING The büS Service interface is located inside the fieldbus gateway. To access, open the cover using a screwdriver. Maintenance work is described in the separate service instructions.
  • Page 49: Accessories

    (M12 to büS service interface micro USB) 773254 Tab. 18: Components USB büS interface set Information on Type 3360, 3361 can be found on the Internet at www.burkert.com • Additional accessories (in the operating instructions), • Spare parts (in the service instructions).
  • Page 50: Packaging, Transport, Storage

    Type 3360 and 3361 Packaging,Transport,Storage PACKAGING, TRANSPORT, STORAGE NOTE! Transport damage. Inadequately protected devices may be damaged during transportation. • Protect the device against moisture and dirt in shock-resistant packaging during transportation. • Prevent the temperature from exceeding or dropping below the permitted storage temperature.