This parameters page is also a good place to check that all batteries are connected and working
properly. In normal working conditions, the current limit is 25A per cell. For example, 75A charge
current limit ( 75 / 25 = 3 ) means there are 3 Pylontech battery modules connected.
6. VE-Direct MPPT Settings
In normal operation the MPPT charge characteristics are governed by the
instructions from the connected Pylontech battery.
This section presumes familiarity with
The settings below are a precautionary measure.
MPPT Parameter Setting
Battery voltage.
48V
Absorption voltage 53V
7. Example Wiring Diagram
Victron Energy - https://www.victronenergy.com/live/
7/11
VictronConnect
Victron & Pylontech US2000, US3000 and Phantom-S
GX device
via DVCC, with