This manual introduces Force-L1 from Pylontech. Force-L1 is a 48Vdc Lithium-Ion Phosphate Battery storage system. Please read this manual before you install the battery and follow the instruction carefully during the installation process. Any confusion, please contact Pylontech immediately for advice and clarification.
1. Safety Precautions Reminding 1) It is very important and necessary to read the user manual carefully (in the accessories) before installing or using battery. Failure to do so or to follow any of the instructions or warnings in this document can result in electrical shock, serious injury, or death, or can damage battery, potentially rendering it inoperable.
5) In case of fire, only dry powder fire extinguisher can be used, liquid fire extinguishers are prohibited; Please do not open, repair or disassemble the battery except staffs from Pylontech or authorized by Pylontech. We do not undertake any consequences or related responsibility which because of violation of safety operation or violating of design, production and equipment safety standards.
Force-L1 lithium iron phosphate battery is one of new energy storage products developed and produced by Pylontech, it can be used to support reliable power for various types of equipment and systems. Force-L1 is especially suitable for application scene of high power, limited installation space, restricted load-bearing and long cycle life.
2.2.3 Control Module FC0048-100 (internal power supply) Control Module (FC0048-100) Display Panel LED Button Short Press Display the LED panel for 20sec. Long Press When status LED fast flash blue ●, loss the button, then it is (more than chosen 115200 baud rate of RS485. 5sec) When status LED fast flash orange ●, loss the button, then it is chosen 9600 baud rate of RS485.
Page 10
Status System Status: blue means working normally; Orange means protection or failure. Blue, slow flashing. Power Relay CLOSE. Alarm exist but can work continue. Blue, lighting. Power Relay CLOSE. Normal. Power Relay OPEN. Normal protection, can recover on Orange, slow flashing. its own (Over Voltage, Under Voltage, etc.).
Page 11
Control Module (FC0048-100) Cable Panel Power Switch Switch A (1P). ON: the battery system’s controller able to turn on. OFF: whole system turns OFF. Switch B (2P). Main breaker. Caution: When the breaker is tripped off because of over current or short circuit, must wait more than 30min then can turn on it again, otherwise may cause the breaker damage.
Page 12
Communication Terminal (RS485 / CAN / RS232 / Link Port 0 / Link Port 1) RS485 Communication Terminal: (RJ45 port) follow RS485 protocol, for communication between battery system and inverter. CAN Communication Terminal: (RJ45 port) follow CAN protocol, for communication between battery system and inverter.
Definition of RJ45 Port Pin RS485 RS232 CANH CANL RS485A RS485B Note: Other Pin must be NULL, if not may influence the communication of system. 11 / 12 19P1FL0801...
Damaged batteries are dangerous and must be handled with the utmost care. They are not fit for use and may pose a danger to people or property. If the battery pack seems to be damaged, pack it in its original container, and then return it to Pylontech or an authorized dealer. NOTE Damaged batteries may leak electrolyte or produce flammable gas.
Page 15
Pylon Technologies Co., Ltd. No. 73, Lane 887, ZuChongzhi Road, Zhangjiang Hi-Tech Park Pudong, Shanghai 201203, China +86-21-51317699 | +86-21-51317698 service@pylontech.com.cn www.pylontech.com.cn...