Hardware Protection Points
In normal operation, the charge parameter limits are set by the Pylontech battery and communicated
through the system by the
Low Voltage: When the battery discharges to 44.5V or less, battery protection will turn on.
High Voltage: If charging voltage above 54V, battery protection will turn on.
Working discharge temperature range is from -10 to 50 degrees celsius.
Charging temperature range is from 0 to 50 degrees celsius.
Discharge Current Limit set to 0A at 47V, inverter will turn off.
Over-charge and Over-discharge Current Limit 102A for 15 seconds, 200A for 0.1 seconds and
400A short circuit current.
If operation is attempted outside the operating range, the battery will disconnect to protect itself.
5. GX Device Settings
On the
GX
device, go to Settings, System setup:
Venus Settings → System Setup Parameter Value
DVCC
Shared Voltage Sense
Shared Temperature Sense
Select the CAN-bus BMS (500 kbit/s) CAN-profile in the CCGX. Menu path: Settings → Services →
CAN-profile.
After properly wiring and setting up, the Pylontech will be visible as a battery in the device list.
If you have multiple batteries a single entry will show up, which represents all batteries:
The parameters option within the battery page shows the actual battery charge and discharge
limits
https://www.victronenergy.com/live/
GX device
to the inverter/charger and MPPT.
ON
OFF
OFF
Printed on 2020-03-09 12:34