Information Display

Via AGU 2.311 Operating Panel
Parameters of Groups b, c, and d are provided upon request only
Display
LMU Functional ID Description
level
Temperatures (specialist level)
b 0
DiagnoseCode
b 1
TkRuec
b 2
Tbwist2
b 3
Tabgas
b 4
TiAussen
b 5
TaGem
b 6
TaGed
b 7
Tvist
b 8
Not assigned
b 9
Not assigned
Process values (specialist level)
c 0
Not assigned
c 1
IonStrom
c 2
Gebl_Drehz
c 3
Gebl_PWM_AusAkt Current blower control (PWM)
c 4
RelModLevel
c 5
Pumpe_PWM
c 6
ek0
c 7
Not assigned
c 8
Not assigned
c 9
Not assigned
Target values (specialist level)
d 0
Not assigned
d 1
Tsoll
d 2
TkSoll
d 3
TsRaum
d 4
TbwSoll
d 5
PhzMax
d 6
NhzMax
d 7
Not assigned
d 8
Not assigned
d 9
Not assigned
30
LMU internal SW diagnostics code
Boiler return temperature
Reservoir temperature at sensor 2 (non existent)
Exhaust temperature
Exterior temperature
Mixed exterior temperature
Dampened exterior temperature
Flow temperature AGU 2.500
Ionization flow
Blower rpm
Relative output
Pump target value (PWM)
Control difference
Target value for 2-point and modulation control
valve (PID)
Current boiler target value
Room temperature target value
Reservoir target value
Maximum degree of modulation during heating
mode
Maximum rpm at maximum output during heating
mode
Note:
By either pushing the "mode" button or
waiting for 8 minutes, the display
automatically reverts back to the
standard display.
1. Push information button.
2. Push buttons
for at least 3 seconds.
3. Use buttons
to select the respective parameter.
1. Push information button.
2. Push buttons
for at least 3 seconds.
3. Push button
4. Push buttons
to select the respective parameter.
1. Push information button.
2. Push buttons
for at least 3 seconds.
3. Push 2x button
4. Push buttons
to select the respective parameter.