Assembly
Electrical Installation
2
3
General Notes
Electrical installations and connections
must be performed by electrical
1
specialists exclusively. Specifications
and regulations of VDE/ÖVE/SEV and
EVU must be complied with.
Dimensioning of power connection
wiring
All external connection wires must not
be stripped more than 30 mm. The hot
lead from strain relief to cleats must
tighten up before the grounded wire in
case they slip out of the strain relief (2).
The wire length must be dimensioned
accordingly. All wires must be routed
around the dividing plate.
Power connection and connection of
customer-provided wiring
The equipment is designed for a fixed
connection and for of type NYM
2
3 x 1.5 mm
or H05W-F 3 x 1 mm
Condensing boiler and switch panel
are wired.
The power connection is made at the
terminal strip (1) of the equipment
using a power circuit intended and
fused for this purpose. All-pole
switches with a contact opening of
> 3 mm or automatic cutout switches
can be used.
Line voltage: 230 V, 50 Hz
Power connection fuse: 10 A
Power consumption: max. 420 W
Power consumption system pump(s)
Max. switching current LMU 1 A / relay
Max. 5 A total
Note:
If TRIGON L is operated with a mixer
circuit connected via AGU 2.500, a
jumper must be installed across lugs
50/51 (X10-01).
en
2
.
15