5 Installation
5-3-2
Product Orientation
The Box PC can be mounted in a book A or wall B C orientation.
• For book mount there is one allowed orientation A .
• For wall mount there are two allowed orientations, horizontally mounted B and vertically mounted
C .
Do not install the Box PC in other orientations.
A
Book mount
Frontview
Sideview
5-3-3
Temperature
The temperature inside a control panel may be at least 10 to 15°C higher than outside the panel. Im-
plement the following measures against overheating at the installation site and in the control panel,
and allow a sufficient margin for the temperature.
Distance for Cooling
Adequate airflow around the IPC Machine Controller is required.
Additional Information
• The ambient temperature must be within the operating range.
Refer to 4-3-1 Operation Environment Specifications on page 4-27 for temperature specifica-
tions.
• Allow space to accommodate for the bending radius of the cables.
• Refer to 3-10 Optional Hardware on page 3-23 for cable bending requirements of cables
advised by Omron.
• Refer to the cable specifications of the supplier for all other cables.
5-16
B
Wall mount
Frontview
Horizontal
NY-series Industrial Box PC Machine Controller Hardware User's Manual (W556)
C
Frontview
Sideview
Vertical