ETC ESR3 Series Installation Manual page 43

Sensor 3 ce rack

Advertisement

Single Pole Racks
For racks which have neutral jumpers fitted, the neutral of the load fed by the emergency module
should be connected to the neutral terminal of an adjacent module.
Neutral Disconnect Racks
In racks without neutral jumpers (Neutral Disconnect racks) the neutral of the load should not be
connected to another load's neutral terminal. This can cause unwanted tripping of RCD modules.
Instead, an auxiliary neutral terminal must be fitted to the neutral plate and the loads should be
connected to the terminal. If your rack was ordered with Emergency Modules the auxiliary neutral
terminal should be factory fitted. If you require an auxiliary neutral terminal, please contact ETC as
shown using the details in
Emergency Modules
Contacting ETC
page
on
6.