Chapter 2
Installation of Racks
Mounting the Rack
• ESR3-12 racks are normally wall-mounted.
• ESR3-24 racks can be mounted to a wall or floor-mounted on an optional pedestal.
• ESR3-36 and ESR3-48 racks are floor standing.
Mounting Racks on a Wall (ESR3-12 and ESR3-24)
The wall must be strong enough to hold the racks. Please see
Specifications, page 36
Step 1:
Step 2:
Step 3:
Step 4:
Installation of Racks
for rack and module weights.
Determine where your rack will be installed using
page 8
and use the appropriate diagram from Figure 1 to mark your mounting holes.
Use the mounting slot dimensions to mark the hole locations. You must supply your own
M10 mounting hardware.
Drill the holes and install the hardware.
Attach the rack to the wall.
375 mm
ESR3-12 rack
481 mm
650 mm
326 mm
203 mm
171 mm
137 mm
Figure 1: ESR3-12 and ESR3-24 wall mount hole diagrams
Appendix A: Sensor3 CE Rack
Figure 1: Sensor3 rack clearances on
375 mm
ESR3-24 rack
925 mm
1213 mm
616 mm
203 mm
171 mm