Operating Guide | VACON® NXI Inverters FI9-FI14
A
C
A The PE conductor and the shield
C The shield
Illustration 11:
Cables with PE Conductors
In all the enclosure sizes, to comply with the EMC standards, use the default values of the switching frequencies.
If installing a safety switch, make sure that the EMC protection continues from the start of the cables until their ends.
The drive must obey the standard IEC 61000-3-12. To obey it, the short circuit power S
interface point between mains and the public mains. Make sure to connect the drive and the motor to mains with a short circuit power
S
that is a minimum of 120 R
SC

6.4 Get Access and Locate the Terminals

6.4.1 Get Access and Locate the Terminals for FI9-FI12

Context:
To open the inverter, for example, for installing the cables, follow these instructions.
Danfoss A/S © 2019.11
B
. If necessary, contact the mains operator.
SCE
B The PE conductors
must be a minimum of 120 R
SC
AQ304441431479en-000101 / DPD00909| 37
Electrical Installation
at the
SCE