Debug Menu (S6.8.7); Using The Expander Board Menu; Expander Board Menu; Examining The Connected Option Boards - Danfoss VACON NXP FI9 Operating Manual

Table of Contents

Advertisement

Operating Guide | VACON® NXI Inverters FI9-FI14
Procedure
1. In the System info submenu, find the Expander boards page (6.8.6) with the Browser buttons.
2. To go to the Expander boards page, push the Menu button Right.
3. To select the board, use the Browser buttons.
If no board is connected to the slot, the display shows no board.
If a board is connected to a slot but there is no connection, the display shows no conn..
4. To see the status of the board, push the Menu button Right.
5. To see the program version of the board, push the Browser button Up or Down.

8.7.9.10 Debug Menu (S6.8.7)

The Debug menu is for advanced users and application designers. Speak to the factory to get instructions, if it is necessary.

8.8 Using the Expander Board Menu

8.8.1 Expander Board Menu

The Expander board menu, that is, the menu for option board information, allows to:
see which option boards are connected to the control board
find and edit the option board parameters.
Table 15: Option Board Parameters (Board OPTA1)
Page
Parameter
P7.1.1.1
AI1 mode
P7.1.1.2
AI2 mode
P7.1.1.3
AO1 mode

8.8.2 Examining the Connected Option Boards

Context:
Use these instructions to examine the connected option boards.
Danfoss A/S © 2019.11
Min
Max
Default
1
5
3
1
5
1
1
4
1
Using the Control Panel
Cust
Selections
1 = 0–20 mA
2 = 4–20 mA
3 = 0–10 V
4 = 2–10 V
5 = –10...+10 V
See P7.1.1.1
1 = 0–20 mA
2 = 4–20 mA
3 = 0–10 V
4 = 2–10 V
AQ304441431479en-000101 / DPD00909| 83

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents