Use these instructions to enable the change when changing the values that are monitored with other values.
Procedure
1. In the Security submenu, find Multimonitoring items page (P6.5.4, Multimon. items) with the Browser buttons.
2. To go to the edit mode, push the Menu button Right.
Change Enabled starts to blink.
3. Use Browser buttons Up and Down to select Change Enabled or Change Disabled.
4. Accept the selection with the [enter] button.

8.7.7 Keypad Settings

8.7.7.1 Finding the Keypad Settings Menu

Context:
Use the Keypad settings submenu in the System menu for making changes in the control panel.
In the submenu, there are 5 pages (P#) that control the panel operation:
Default page (P6.6.1)
Default page/Operating menu (P6.6.2)
Timeout time (P6.6.3)
Contrast adjustment (P6.6.4)
Backlight time (P6.6.5)
Procedure
1. In the System menu (M6), find the Keypad settings submenu (S6.6) with the Browser buttons.

8.7.7.2 Changing the Default Page

Context:
Use the Default page to set the location (page) to which the display automatically moves after the Timeout time or after the panel is set
on.
For more information on the timeout time, see
If the Default Page value is 0, the function is not activated. When the Default page is not used, the control panel shows the page that
was last showed on the display.
Procedure
1. In the Keypad settings submenu, find the Default page subpage (P6.6.1) with the Browser buttons.
2. To go to the edit mode, push the Menu button Right.
3. To change the number of the main menu, use the Browser buttons.
4. To edit the number of the submenu/page, push the Menu button Right. Change the number of the submenu/page with the
Browser buttons.
5. To edit the third level page number, push the Menu button Right. Change the number of the third level page with the Browser
buttons.
6. To accept the new default page value, push the [enter] button.
76 | Danfoss A/S © 2019.11
8.7.7.4 Setting the Timeout
Time.
Using the Control Panel
AQ304441431479en-000101 / DPD00909