Operating Guide | VACON® NXI Inverters FI9-FI14

8.7.8.7 Changing the Number of Retries to Receive HMI Acknowledgement (P6.7.4)

Context:
Use this parameter to set the number of times the AC drive tries to receive acknowledgement if it does not receive it during the
acknowledgement time (P6.7.3) or if the received acknowledgement is defective.
Procedure
1. In the Hardware settings submenu, find the Number of retries to receive HMI acknowledgement (P6.7.4) with the Browser buttons.
2. To go to the edit mode, push the Menu button Right. The value starts to blink.
3. To change the number of retries, use the Browser buttons.
4. To accept the change, push the [enter] button.

8.7.8.8 Sine Filter (P6.7.5)

When using an old motor or a motor that was not made to be used with an AC drive, it can be necessary to use a sine filter. A sine filter
makes the sine form of the voltage better than a dU/dt filter.
If a sine filter is used in the AC drive, set this parameter to Connected to put it into operation.

8.7.8.9 Pre-charge Mode (P6.7.6)

For an FI9 or a larger inverter unit, select Ext.ChSwitch to control an external charge switch.

8.7.9 System Info

8.7.9.1 Finding the System Info Menu

Context:
The System info submenu (S6.8) contains information on the hardware, software, and operation of the AC drive.
Procedure
1. To find the System info submenu, scroll down in the System menu until the location indication S6.8 shows on the first line of the
display.
2. To go to the System info submenu from the System menu, push the Menu button Right.

8.7.9.2 Total Counters (S6.8.1)

The Total counters page (S6.8.1) has information on the AC drive operation times. The counters show the total number of MWh,
operation days, and operation hours. The Total counters cannot be reset.
The Power On time counter (days and hours) always counts, when the AC power is on. The counter does not count when control unit
runs on +24 V only.
Table 13: Total Counters
Page
Counter
C6.8.1.1.
MWh counter
80 | Danfoss A/S © 2019.11
Example
Using the Control Panel
AQ304441431479en-000101 / DPD00909