Connecting the EBM(s)

3 3 . . 6 6
C C o o n n n n e e c c t t i i n n g g t t h h e e E E B B M M ( ( s s ) )
A small amount of arching may occur when connecting an EBM to the UPS. This is normal and will not harm
personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
1.
Plug the EBM power cable(s) into the battery connector(s). Up to 4 EBMs may be connected to the UPS.
2.
Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each
cable.
3.
Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
Figure 7. 9PXEBM Rack Mount Connections
9PXEBM48
NOTE
18
Eaton 9PX Lithium-Ion
EBM Communications wiring
UPS
Battery Comm
Battery Comm
Battery Comm
Battery Comm
The EBM communication wiring connections are directional and must be connected in
the correct sequence to ensure proper detection, regulation and lifecycle monitoring of
the integrated battery management system (BMS).
P-164001006—Rev 01
CAUTION
9PXEBM72
EBM 1
EBM 2
EBM 3
EBM 4