Eaton 9PX Lithium-Ion Advanced User's Manual page 16

Hide thumbs Also See for 9PX Lithium-Ion:
Table of Contents

Advertisement

User Settings
Table 6. User Settings (Continued)
Battery settings
Com settings
10
Eaton 9PX Lithium-Ion
Available settings
Submenu
to Disabled, shutdown sequence will
not complete, UPS stays on.
[Enabled] [Disabled]
[Timer] [1min] ... [15min]
[Level] [100W] ... [1000W]
Energy saving
If Enabled, UPS will shut-down after
defined duration. of back-up time, if
load is less than set value.
[Enabled] [Disabled]
[Timer] [10min] ... [120min]
If Disabled, LCD and communication
Sleep mode
will turn OFF immediately after UPS is
OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
[Enabled] [Disabled]
Site wiring
Prevents from starting the UPS in case
fault
of phase vs neutral wires swapping.
[Enabled] [Disabled]
If Enabled, activates a confirmation
Power Off alert
screen that requires user confirmation
after pressing the power button,
before the UPS shutdown occurs.
[Capacity] [0%] ... [100%]
[Runtime] [0min] ... [60min]
Low battery
The alarm triggers when the set
warning
percentage of battery capacity or
remaining back-up time is reached.
[0%] ... [100%]
Restart bat.
If set, automatic restart will occur only
level
when percentage of battery charge is
reached.
[ROO] [RPO] [DB9–4}
Sets Input signals parameters
(function, delay, operation) through
external contact connectors or RS232.
ROO port:
- [Function]: [No] [ROO] [RPO] [Building
Input signals
alarm] [Forced bypass] [On generator]
[Remote shutdown]
- [Delay]: [0s] ... [999s]
- [Active]: [Open] [Closed]
RPO port:
P-164001006—Rev 01
Default settings
[Disabled]
[5min]
[100W]
[Enabled]
[90min]
[Disabled]
[Enabled]
[0%]
[3min]
[0%]
[No]
[0s]
[Closed]